Seiteninhalt
FAQ
What torque should be used to tighten the connections?
M6 screw -> 10 Nm
Is the BEL-TS suitable for 60 Hz?
this is specified in the technical description on your order
Mains voltage: xxx V, 50/60 Hz
Supply voltage: xxx V, 50/60 Hz
Fan voltage: xxx V, 50/60 Hz
The BEL-TS is operated above an altitude of 2500 m. What needs to be taken into account?
As altitude increases, there is a reduction in performance
e.g. 125 kvar -> 104 kvar
A correction factor of 1.075 is applied to the voltage e.g. 480V -> 445 V
Is it possible to switch phases L1 and L2 instead of phases L1 and L3?
Yes, it is also possible to switch phases L1 and L2.